by Thermo 20. June 2012 16:28

Dielectric II

In Dielectric I, I provided the first part of a four-part answer to a query from Alabama – the summary question: To what extent does the introduction of injection equipment into energized devices impact the safe operation of medium voltage circuits? We learned that there are great differences in the extent of this risk depending upon the injection paradigm employed. In fact there are three injection paradigms and at Novinium we use only the safest processes. With Novinium’s patented SPR (sustained pressure rejuvenation) there is zero additional risk. With Novinium’s iUPR (improved unsustained pressure rejuvenation) process the risk is many times less than the legacy approach used by others. The legacy paradigm is called UPR (unsustained pressure rejuvenation). In this post I provide data to show why the feed end of an iUPR injection is not a safety issue – unfortunately the same conclusion is not true for the legacy UPR process.

In the illustration nearby I am standing next to iUPR injection equipment. From left to right are …

A CO2 cylinder enclosed in a PVC bag provides energy to urge fluid into the cable strands.  A polyethylene CO2 supply tube provides about 20 psig of pressure to the predominantly plastic feed tank. At least three feet of polyethylene fluid supply tube with a wall thickness of 100 mils delivers fluid to an injection adapter and a mated injection elbow. In another case not illustrated, the fluid might be supplied to a live-front injection adapter. Whether dead-front or live-front, the fluid comes in direct contact with an energized conductor. The fluid is a dielectric, and with Novinium’s improved unsustained pressure rejuvenation process, the flow is one way – toward the termination. This one-way flow provides assurance that there is no fluid contamination from backward flow as suffered by legacy approaches. At Cable Technology Labs (CTL) the leakage current in a column of Ultrinium™ 732/40 fluid was measured between two electrodes at 15, 25, and 35 kV. The leakage current was steady at about 0.03 mA, 0.04 mA, and 0.05 mA for 15, 25, and 35 kV respectively from 14 feet of electrode separation down to less than 1 foot.

With the Novinium iUPR process there are no ground electrodes ever in direct contact with the fluid. The fluid flows though several feet of PE tubing with a wall thickness of 100 mils. The AC breakdown strength of the PE is at least 800 volts/mil and hence the AC breakdown strength of the tubing is greater than 80 kV. The fluid flows from a polypropylene/acetal tank with even thicker walls than the tubing. The closest ground plane is typically the concrete or earth on which the feed tank rests. Novinium has deployed these iUPR systems thousands and thousands of times and there have been zero issues. We wrap the CO2 cylinder in a PVC bag to prevent accidental contact with exposed secondary voltages.

In my third post in the series, Dielectric III, I will discuss the design issues of the vacuum tank designed for iUPR and the features that make iUPR the second safest injection approach. Finally, in Dielectric IV, I will address the equipment separation issues Alabama raises in his questions, 6 through 8.

Dielectrically delighted,

T. B. Frog

Tags: , , , ,

Safety Matters

by Thermo 19. June 2012 13:56

Dielectric I

Dear Wisest Webbed one,

I am working on my comments/concerns for the Safety Section for the C30 Draft Guide [Editors note: C30 is a group within the IEEE/PES/ICC working towards the writing of a “Draft Guide for Rehabilitation and Rejuvenation of Extruded Dielectric Cable Rated 2.5 kV through 46 kV.” While that Draft is being crafted, interested readers may wish to review a Novinium published early version undertaken at the behest of the group’s chair, which is available at www.novinium.com/Standards.aspx.], and have a few questions. Just because the equipment is all or mostly plastic materials, these questions still need to be explored and discussed.

  1. What is the insulation rating of the fluid(s) that you use for injecting?
  2. What is the insulation rating of the hose(s) you use from your canisters to the injection point?
  3. What is the insulation rating of the canisters themselves?
  4. What is the insulation rating for the combination elbow/canister?
  5. Do you have the test data for these pieces of equipment? Will you share the test data with the group?
  6. Have you looked at the electrical separation distance from your canisters to the cover or live bushing?
  7. Have you looked at the electrical separation distance from your canisters to ground wires in the equipment?
  8. Have you looked at the electrical separation distances from your canister connected to one phase and to the other phases in a three phase installation?

Your froguidance would be appreciated.

Alabama detailed draft

Dear Alabama-

I don’t know about you, but the fact that the first three letters in dielectric spell “die” makes me want to take extra measure to assure the safety of all who use dielectric enhancement technology. The heart of your eight questions can be summarized thusly: To what extent does the introduction of injection equipment into energized devices impact the safe operation of medium voltage circuits? Before I answer that question generally and some of your more specific questions, it is important to recognize that there are three distinct methods of dielectric enhancement fluid injection and two conductor realms in which those methods are deployed. Ordered from oldest to most advanced, the three methods are:

    UPR ♦ Unsustained Pressure Rejuvenation,

    iUPR ♦ improved Unsustained Pressure Rejuvenation, and

    SPR ♦ Sustained Pressure Rejuvenation.

To learn more about the details of these rejuvenation methods, check out my June 18, 2010 post titled “How to Inject.” Novinium is synonymous with safety, so we use the two most advanced processes almost exclusively. In the very unusual cases where Novinium leaves injection devices attached to energized devices for more than a couple of days, equipment designed specifically for that case is deployed. Because it is a rare case, I refer interested readers to my April 15, 2001 post, “Soaking II: Safety First” for more details.

In this series of posts, I focus on the cases most important to circuit owners. In the table nearby the implementation of the three injection methods are compared for the two conductor cases, namely small conductor and large conductor. Small conductors include stranded conductors, generally with 19 or fewer strands. Note that for large conductors, cables are injected de-energized whichever injection method is utilized, and hence your questions are moot for these large conductors. Further, SPR is applied over 99% of the time to deenergized cables, and hence the questions are again largely moot. The only firm in the world that can deliver iUPR and SPR is Novinium, because we own the intellectual property on the methods and chemistry that make those processes possible. For most injection work we undertake, we operate in the green … my favorite color.

When we do inject into energized devices we mitigate the risks about which you are inquiring by limiting the period that injection equipment is connected to energized components. In the red portion of the table, older technology requires extensive soak periods spanning several months. At first glance you might assume that reducing the period of time by sixty-fold would reduce the exposure to the risk by sixty-fold, but you would be underestimating the impact. In the iUPR process, fluid flows in only one direction. A feed bottle with a positive pressure, typically about 20 psig, is attached to one cable end and a vacuum bottle with a negative pressure of around -10 psig is attached to the other cable end. Fluid flows from high to low pressure. Both the feed tank and the vacuum tank are removed concurrently. Thus on the feed side, fluid with a high dielectric strength flows through tubing made of a high dielectric polymer and there is a negligible probability of substantive current flow. I’ll provide some data in my second post, Dielectric II.  With iUPR the only substantive design issue is on the vacuum or outlet side, there is no way to be certain what will come out of the outlet, so we have to assume that it will be water. In practice, water seldom comes out of 7-strand or 19-strand cables (To learn why, click here.), but from a design perspective this is the worst-case assumption.

UPR has the same worst-case on the outlet end, but it also suffers from a more insidious issue on the inlet end. I examined this issue in some detail in my April 15, 2011 post, “Soaking II: Safety First.” You should read that post, but in summary, UPR suffers a risk that conductive contaminants will render the feed fluid conductive. The worst-case assumption on the inlet side is about the same as the on the vacuum side, but the feed is connected for 60 days or more. This risk is recognized by the practitioners of UPR, because they explain the risk and a potential solution to mitigate the risk in U.S. Patent 7,704,087 of April 27, 2010. Amazingly after exposing the risk those practitioners have not implemented their mitigation strategy. I usually speak only of technical matters, but you don’t have to have a law degree to recognize that if you know about a safety problem, but do nothing to mitigate the issue – your liability undoubtedly increases. Risk managers should take this knowledge into account as they make their choice between the various injection processes. If your firm believes in safety as the most important criteria, don’t utilize UPR.

In my next post (Dielectric II), I will provide some data to show why the feed end of an iUPR injection is not a safety issue. In my third post in the series (Dielectric III), I will discuss the design issues of the vacuum tank designed for iUPR and the features that make iUPR the second safest injection approach. Finally, in Dielectric IV, I will address the equipment separation issues you raise in your questions, 6 through 8. For a thorough description of all of the rejuvenation dimensions of safety check out the 89-page treatise, “A Comparison of Rejuvenation Hazards & Compatibility.”

Practicing safe rejuvenation,

T. B. Frog

Tags: , , , ,

Safety Matters

by Thermo 6. September 2011 15:05

Integrated Rehabilitation

 

In my September 2, 2011 post, I replied to a Connecticut fan that inquired on the prudence of flowing through legacy splices.  At the end of that post I promised to explain integrated rehabilitation – the ultimate approach to rehabilitating underground cables. When it comes to rehabilitating aging underground power cables there are basically three tool choices:  A good choice, a better choice, and the best choice.  The only bad choice is to do nothing at all.

 

Good

 

Replacing aging cables and associated components is a good choice.  The post replacement reliability is likely to be better than 99%. Most post-replacement reliability issues are likely to be craftsmanship. The dark sides of replacement include its capital inefficiency, its negative environmental impact, and the disruption to electrical customers as heavy equipment moves around their neighborhoods.  No matter how the legacy cable was buried (i.e. direct buried, in conduit, single phase or multi-phase) it will require at least twice as much capital to replace as required to rejuvenate. Particularly for direct buried cable, which is typically abandoned in place, all the copper, aluminum, and polymer must be replaced with new natural resources, suffering a considerable carbon footprint.

 

Better

 

Rejuvenation is like recycling cable in place and at a fraction of the cost of replacement.  Unsustained pressure rejuvenation or UPR, has been practiced for over two decades.  Post-injection reliability is on a par with replacement and anticipated life of two decades or more is possible.  When splices are encountered, an attempt is made to flow through those splices with varying degrees of success.  Some circuit owners have great success; others have dismally low success. On average, about half of the splices encountered support flow.  Improved UPR or iUPR was introduced in 2008 by Novinium. Improved UPR eliminates the soak period used in the original UPR approach.  Elimination of the soak period improves the safety and the economics of the UPR injection paradigm.

 

Best

 

Introduced in 2005, Sustained pressure rejuvenation or SPR enjoys numerous safety and operational advantages over UPR. Most significantly …

 

1.   Exposure to energized components is reduced several-fold from UPR making the process inherently safer.

2.   Dielectric properties increase about 87-times faster than with UPR or iUPR. This means even higher post-injection reliability.

3.   Even single-section, post-failure injection is authorized to be capitalized by the FERC and RUS.

4.   A single visit to a cable segment means minimal disruption to electrical end-users.

 

With these three tools in our rehabilitation toolbox, Novinium draws the right tool for the job.  Because SPR enjoys the greatest capital efficiency and the highest post-rehabilitation reliability, it is applied to as many cables as possible.  The vast majority of cables are rehabilitated this way.

 

Occasionally, a splice, which will support flow, is pinpointed in a location too difficult to excavate. For these cases, iUPR is utilized. In spite of the compromises associated with flowing through splices, iUPR is still more capital efficient than replacement and has a similar post-injection reliability for a couple of decades.

 

Finally, where there is widespread neutral corrosion or too many splices, the most capital intensive replacement tool is utilized.

 

The key to the unmatchable economics of the integrated approach is the minimization of replacement. Worldwide there is a single rehabilitation supplier capable of providing the fully integrated rehabilitation approach – Novinium. Novinium founders invented UPR, iUPR, and SPR, so there is nowhere else that circuit owners can access the world’s foremost experts.

 

Using the right tool for the job,

T. B. Frog

Tags: , , , , , , ,

Operational Considerations

by Thermo 15. April 2011 22:21
Soaking II:  Safety First
 
Dear Greatest of Soakers,
 
It seems odd to me that for one who spends so much time soaking herself, that soaking cables is anathema to your firm’s culture.  When is it appropriate to soak a No.2 compressed URD cable?  If I do soak, for how long should I soak?
 
Geometrically constrained,
 
Alaskan Amber
 
Dear Amber-
 
I provided a first installment of my thoughtful answer to your question in “Soaking:  Diminishing Returns I.”  In that first post, I drove a stake into the heart of the myth that Novinium never soaks, and I provided the background to explain why it is seldom necessary to do so.  In this second post I will explain why soaking is so very dangerous when performed the old way.
 
I could explain the safety issue in my own pithy way, but instead I copy below the words of Messrs. Stagi and Steele of UTILX Corporation.  They were granted U.S. Patent 7,704,087 about one year ago.  The patent is titled, “Check Valve for Charge Tanks.”  They have undoubtedly experienced the dangers posed by soaking.  I assume those experiences motivated their invention.  To wit (beginning on column 1, line 45) …
 
The fluid is commonly injected into underground cables from a fluid feed line, which is connected to a fluid feed tank, at the injection termination.  When fluid is injected into the cables at the injection port of the injection terminations, it is assumed that the fluid flow is only in one direction, flowing from the feed tank to the cable. However, as the cable fills and the fluid system begins to stabilize, temperature changes that occur inside the cable or outside in the environment around the feed tank can cause the pressure of the system to fluctuate.  The pressure fluctuations can lead to instances where the pressure inside of the injection elbow is greater than the pressure inside of the fluid feed tank. At this point, fluid flow would reverse, moving from the injection elbow back into the fluid feed tank.
The fluid that travels in the reverse direction, out of the injection elbow, carries contaminants from the cable to the feed tank. These contaminants can be conductive or semiconductive, effectively reducing the insulating value of the remediation fluid in the fluid feed line that separates the energized cable from the feed tank and a conductive pathway can be formed.
 
I don’t always agree with the gentlemen from UTILX.  Lacking an amphibian influence, they seem to me to be prone to error, but this time they have eloquently defined the issue.  Fluid can flow backward through the feed tubing during the soak period.  An energized tube and feed tank may flash to ground, may start a fire or worse yet an explosion, and, if anybody is nearby, the unfortunate event might injure or even kill them!  At Novinium we are not willing to take those kinds of risks.  I hope my colleagues at UTILX implement their ‘087 invention before there are any new events.
 
As mentioned in my last post, Novinium can and does greatly mitigate these risks in live-front applications with a piece of proprietary technology called an HVFI or high-voltage fluidic-interface.  Click here to view a HVFI test report, which includes a detailed description of how it works.
 
If you really, really want to soak in dead-front applications, my mechanical engineers and I will develop a system that is much safer.  Of course, using non-flammable Novinium fluids helps a lot, but we can do even better.  When you see how a frog solves this problem, you will see elegance embodied.  Stand by for more on this subject.
 
Safety First,
Thermo

Tags: , , ,

Operational Considerations | Safety Matters

by Thermo 31. March 2011 16:23

Soaking I:  Diminishing Returns

 

Dear Greatest of Soakers,

 

It seems odd to me that for one who spends so much time soaking herself, that soaking cables is anathema to your firm’s culture.  When is it appropriate to soak a No.2 compressed URD cable?  If I do soak, for how long should I soak?

 

Geometrically constrained,

Alaskan Amber

 

Dear Amber-

 

You ask more questions than any of my other numerous fans.  I like that, except I have been told that some find the questions and the answers too technical.  My response to those critics is to ask your own questions.  If you ask a simple question, I will provide a simple answer.  This Amber guy is cool, his question is appropriate, and a proper answer it is going to require two posts.  Here is the first …

 

I can see why you might have been misled to believe that I am anti-soak, but that characterization is unfair.  Let’s set the facts straight:

 

1.   Novinium has a pile of patents that make soaking unnecessary, even for multi-decade life, for all but the most geometrically constrained cables.  I will define “geometrically constrained” later.  The following technological advancements, which I have expounded upon in past blogs, mean that even without a soak, Novinium technology will last longer than the two-decade old approach used by less enlightened purveyors of rejuvenation:

a.   Catalyst improvements were chronicled in Catalytic Considerations I and Catalytic Considerations II.

b.   Novinium Voltage Stabilizers are not present in older approaches.

c.    Our ultra-violet package, which retards the formation of electrical trees was laid out in “To UV or not to UV.”

d.   The tremendous power of effective anti-oxidants present only in Ultrinium™ brand fluids was described in “AO, AO … its home from work we go.”

e.   Chain Entanglement” dramatically slows the exudation of treatment fluid from the cable and is another patented Novinium innovation.

f.     The “Really Long Term Life” afforded by still another patented Novinium innovation delivered by an ultralow permeability component.

2.   The folks at Novinium invented soaking over two decades ago.

3.   Novinium does soak cables under certain circumstances.

 

We do consider soaking as a last resort, however, because soaking has two drawbacks.  First, and in order of importance to us, there are safety compromises associated with leaving a hydraulic connection to an energized cable for a long period of time.  I enumerated these risks in my post:  Greatest Rejuvenation Risks.”  For live-front applications, Novinium can greatly mitigate these risks with a piece of proprietary technology called an HVFI or high-voltage fluidic-interface.  Click here to view a HVFI test report.  Second, there are economic costs associated with a soak period.  In short, a soak bottle with an associated capital cost must be deployed for the duration of the soak period and the injection team has to be redeployed to the site to remove said soak bottle.

 

Despite these challenges we occasionally resort to soak periods.  The very first consideration is whether the cable to be rejuvenated has a severely constrained geometry.  The “Draft Guide for Rehabilitation and Rejuvenation of Extruded Dielectric Cable” defines constrained geometry in general and severely constrained geometry in particular as follows:

 

“When the available volume of fluid that can be held in the strand interstices at atmospheric pressure is less than the optimum quantity of fluid to treat the cable, the cable is said to be a constrained geometry cable.  Figure 3-1 [below] shows the three realms of geometry for round (or concentric), compressed, and compact strand cables, namely unconstrained (greater than 20 kg/km), moderately constrained (<20 kg/km and >10 kg/km), and severely constrained (<10 kg/km).

 

In practice severely constrained cables are those with conductors of 7-strand and compact 19-strand construction.  If your cables do not have severely constrained conductors, four decades of life extension are possible without resorting to soak periods.

 

At Novinium we routinely employ soak periods on severely constrained geometry cables for high value circuits with live-front terminations.  Submarine cables provide an example of such high value circuits.  These cables can require 7-figures to replace, so the incremental cost of providing a soak is justified.  Can Novinium make soaking safe in the dead-front applications typical of residential distribution cable?  To answer that question check out my subsequent posts in this series:

 

Soaking II:  Safety First

 

Unconstrained by old paradigms,

Thermo

Frog Blog

Month List